• 8 Field
selectable sequences
• All Common ISA sequences Including First-Out
• Switch, Transistor, and Logic Level Inputs
• 4 or 8-Point Monitoring
• Free Custom Message Labels
• Type 4X, NEMA 4X, IP65 Front
• Universal Power Supply 85-265 VAc
• 12-36 VDC/12-24 VAC Power Option
• Built-In 85 dB Horn
• 2 SPDT Relays for Alarm Activated Devices
• 24 VDC Isolated Power Supply (AC Models)
• Multiple-unit First-Out Indication
• Silence, Acknowledge, and Reset Functions
• Sunlight Readable Indication
• Shallow Depth 1/8 DIN case
The Vigilante® II can be programmed for multiple sequences with
first-out alarm indication. This feature indicates the first point of
failure of a system when multiple alarms occur. If multiple Vigilante® II
annunciators are connected for multiple unit first-out indication, only
one input from all connected devices will display as a first-out alarm.
The Vigilante® II Alarm Annunciator can be programmed for all common ISA
sequences including A, F1A, F2A, F3A, M, F1M. Selectable ISA -1 (Silence
Button), -4 (No Lock-
In), and horn disable options.